Fire resistance requirements for rubber-tire warehouses

Download
  1. (PDF, 5 MB)
  2. Get@NRC: Fire resistance requirements for rubber-tire warehouses (Opens in a new window)
DOIResolve DOI: http://doi.org/10.1007/BF01470862
AuthorSearch for: ; Search for:
TypeArticle
Journal titleFire Technology
ISSN0015-2684
Volume27
Issue2
Pages100112; # of pages: 13
SubjectFire; fire modeling; fire resistance; rubber tires; warehouses; Performance of:
AbstractThe normalized heat load approach is used to analyze the severity of warehouse fires involving a large volume of rubber tires. The results suggest that for a compartment with a fire resistance ratingof two hours, the maximum number of tires that can be stored safely per square meter of compartment surface area is 0.8 to 1.2for normal weight concrete walls, and 0.4 to 0.7 for lightweight concrete walls.