Correlation between the severities of the ASTM E119 and ISO 834 fire exposures

Download
  1. (PDF, 606 KB)
  2. Get@NRC: Correlation between the severities of the ASTM E119 and ISO 834 fire exposures (Opens in a new window)
DOIResolve DOI: http://doi.org/10.1016/0379-7112(88)90011-2
AuthorSearch for: ; Search for:
TypeArticle
Journal titleFire Safety Journal
ISSN0379-7112
Volume13
Issue2-3
Pages16368; # of pages: 96
Subjectfire resistance tests; temperature; castable refractory brick specimen; standards; fire endurance gain; Fire; essai de résistance au feu
AbstractThe temperature rise in a castable refractory brick specimen of well-defined thermal properties was used to develop a correlation between the severities of the ASTM E119 and the ISO 834 fire tests. It was found that the ISO fire test is slightly less severe than the ASTM test, but the gain in fire endurance on account of conducting the test according to the ISO standard is usually five minutes or less.