Column covers: a practical application of sheet steel as a protective membrane

Download
  1. (PDF, 1 MB)
  2. Get@NRC: Column covers: a practical application of sheet steel as a protective membrane (Opens in a new window)
AuthorSearch for:
TypeArticle
Journal titleFire Study
ISSN0077-5495
Volume27
Pages26
SubjectFire
AbstractTwo fire tests on structural steel columns protected by standard gypsum wallboard held in place with sheet steel column covers are described. The tests showed that sheet steel column covers are able to retain the gypsum board for much longer periods of fire exposure than other mechanical fastening methods.The fire endurance classifications developed were 1 1/2 hr and 2 hr, for two layers of 1/2-in. and two layers of 5/8-in. standard wallboard, respectively.