Small-scale fire test of 6 inch wall penetrated by telephone cables

Download
  1. (PDF, 1 MB)
  2. Get@NRC: Small-scale fire test of 6 inch wall penetrated by telephone cables (Opens in a new window)
AuthorSearch for:
TypeArticle
Journal titleBuilding Research Note
ISSN0701-5232
Volume116
Pages7
Subjecttelephone devices; electric cables; fire tests; Fire; téléphone (dispositif); cable éléctrique; essai au feu
AbstractA positive pressure fire test was carried out on two small- scale 6 in. thick, high-temperature concrete walls penetrated by 13 multi-core and 6 coaxial telephone cables. Alumina-silica-ceramic bulk fibre, capped at the exterior face with cementitious sealant, constituted the firestopping around the cables. The penetrations proved satisfactory except for those involving the two largest cables, which gave unacceptably high temperatures after approximately 2 hr of test. Sealing the ends of the cables could have further improved performance.