Small-scale fire tests of walls penetrated by telephone cables

Download
  1. (PDF, 771 KB)
  2. Get@NRC: Small-scale fire tests of walls penetrated by telephone cables (Opens in a new window)
AuthorSearch for:
TypeArticle
Journal titleFire Technology
ISSN0015-2684
Volume11
Issue2
Pages7379; # of pages: 7
Subjectfire resistance tests; walls; conduit cable sleeves; Fire; essai de resistance au feu; mur; manchon de cable electrique
AbstractFour small-scale fire-resistance tests have been carried out on walls penetrated by telephone cables. The failure criteria were that temperature should not exceed 1000 degrees F at the unexposed surfaces of the cable, sleeve or wall, nor should openings greater than 0.1 square inch develop.