A comparison of two current transformer calibration systems at NRC Canada

Download
  1. Get@NRC: A comparison of two current transformer calibration systems at NRC Canada (Opens in a new window)
DOIResolve DOI: http://doi.org/10.1109/TIM.2016.2631739
AuthorSearch for: ; Search for: ; Search for: ; Search for: ; Search for: ; Search for: ; Search for:
TypeArticle
Journal titleIEEE Transactions on Instrumentation and Measurement
ISSN0018-9456
1557-9662
Volume66
Issue6
Pages16281635
SubjectAC current measurement; calibration; current comparator; current transformer; measurement uncertainty
AbstractA comparison of two systems based on different methods for calibration of current transformers at several different transformation ratios, burdens, and power frequencies of 60 Hz and 50 Hz is performed at the National Research Council of Canada. The obtained discrepancies in ratio and phase errors are within 5 μA/A and μrad, respectively, for small test currents and less for larger test currents.
Publication date
PublisherIEEE
LanguageEnglish
AffiliationMeasurement Science and Standards; National Research Council Canada
Peer reviewedNo
NPARC number23002557